Tell : 0086 135 1058 5626            E-mail :  info@nasn.cn
UPS Vs EPS: The Essential Differences And Application Scenarios between Uninterruptible Power Supply And Emergency Power Supply
You are here: Home » News » UPS Vs EPS: The Essential Differences And Application Scenarios between Uninterruptible Power Supply And Emergency Power Supply

UPS Vs EPS: The Essential Differences And Application Scenarios between Uninterruptible Power Supply And Emergency Power Supply

Views: 0     Author: Site Editor     Publish Time: 2025-11-20      Origin: Site

facebook sharing button
twitter sharing button
line sharing button
wechat sharing button
linkedin sharing button
pinterest sharing button
whatsapp sharing button
sharethis sharing button

In the fields of communication, data centers, and building power distribution, UPS (uninterruptible power supply) and EPS (emergency power supply) are two crucial types of power supply equipment. They may appear to have similar functions, but in reality, their design concepts, technical principles, and application scenarios are vastly different. Choosing the wrong device can result in wasted investment or loss of critical load protection.


Core principle: From "constant protection" to "emergency start-up" 

1. UPS (uninterruptible power supply)

Its core design goal is to provide high-quality, uninterrupted power. Taking the most mainstream dual conversion online UPS as an example: Normal: After the mains power is input, it is first converted into DC power through a rectifier, which is used for float charging of the battery and converted into pure and stable AC power output to the load through an inverter. The load is powered by the inverter at all times. Switching: In case of mains power failure, the battery seamlessly takes over, and the DC power continues to supply the load through the inverter, achieving zero interruption (0ms). After the mains power is restored, switch back to the rectifier for power supply and charge the battery. 

Key: The inverter continues to work online and is the "personal bodyguard" of the load.


2. EPS (Emergency Power Supply)

Its core design goal is to provide safe and reliable emergency power in the event of a power failure, emphasizing high reliability, long delay, and adaptability to large loads. Normal: When the mains power is normal, it directly supplies power to the load through the interconnection device, and the inverter is in a cold standby or shallow charging standby state. The system efficiency is extremely high (>98%) and the energy consumption is extremely low. Switching: When the mains power is abnormal (power outage, over limit), the controller quickly starts the inverter and switches to the inverter output through the interlock switch. This process involves switching times, typically ranging from milliseconds to seconds (such as fire protection requirements<0.25s, and special load requirements such as metal halide lamps requiring even shorter times). 

Key: The inverter does not work normally and plays the role of an "emergency generator".


Main differences




UPS EPS
Chief function Uninterrupted and purified electricity Emergency power supply and safe evacuation
Inverter status Continuous online operation Offline standby, mains power failure startup
Switch time 0 milliseconds (online) Milliseconds to seconds (with interrupts)
Output waveform Usually pure sine wave (online) Mostly sine waves, some square waves/step waves
Load adaptability Mainly for capacitive loads such as IT and precision instruments Inductive and mixed loads such as motors and lighting fixtures
Overload capacity Weak (usually 105-125%, short-term) Extremely strong (up to 120-150% sustained, or several times impact)
Work mode Continuous operation Intermittent emergency operation
Efficiency Low (90-97%, with loss) Extremely high (>98%, minimal standby loss)
Management monitoring Fine and complex, emphasizing real-time performance Relatively simple, emphasizing reliability

Application


1. The battlefield of UPS (related to "business continuity"): information continuity assurance

Data center/server room: Protect servers, storage, and network equipment to prevent data loss and business interruption.

Communication core network/transmission nodes: Ensure uninterrupted communication 24/7.

Precision medical equipment (such as CT, MRI): Ensure stable operation of the equipment and secure inspection data. Industrial Automation control system: prevent sudden shutdown of the production line from causing huge losses.

Financial trading system: Every millisecond interruption can mean huge losses.

2. EPS battlefield (related to "life safety"): life safety and emergency lighting

Fire emergency lighting and evacuation indication system: mandatory application, providing lighting for personnel evacuation. Power supply for fire power equipment such as fire elevators, smoke exhaust fans, and fire-resistant rolling shutters.

Public emergency lighting for large venues, theaters, and shopping malls.

The emergency power supply for high-power special lighting (such as metal halide lamps) requires special attention to the fast switching version.

In industrial production, supplying power to process flows that require safe shutdown to avoid accidents.

UPS Vs EPS The Essential Differences And Application Scenarios between Uninterruptible Power Supply And Emergency Power Supply

ABOUT NASN

GUANGZHOU NASN POWER CO.,LTD is a professional EV charger, DC power supply and battery storage solution provider and enterprise in China, a wholly owned subsidy of NASN ELECTRONICS (HONGKONG) CO., LIMITED.

QUICK LINKS

PRODUCT CATEGORY

CONTACT US

   Contact person : Florence
   Tell : +86-20-86857678
    Phone : +86-135 1058 5626
    QQ : 28243245
    E-mail : info@nasn.cn
Copyright ©️ 2022 GUANGZHOU NASN POWER CO., LTD.  Technology by LeadongPrivacy Policy. Sitemap.