Views: 0 Author: Site Editor Publish Time: 2024-05-17 Origin: Site
19'' rack mounted modular rectifier 48VDC 30A/24VDC 6A rectifier module system is available from NASN POWER.
Communication with Modbus
Communication with SCADA
Protection over current input/output/short circuit
Battery external to backup

| Parameter type | Parameter name | description | 
| AC input | Input voltage | Three-phase 380V AC three-phase four-wire Input range: 147V AC~519V AC (line voltage) 85V AC~300V AC (phase voltage) | 
| Frequency | 45Hz~ 66Hz, rated at 50Hz/60Hz | |
| Factor | Under rated load conditions≥ 0.99 | |
| DC input | Default Input voltage | 53.5V DC | 
| Input voltage range | 43.2V DC~57.6V DC | |
| -48VDC output | Voltage regulation accuracy | ≤±0.6% | 
| Output voltage range | –42V DC~–58V DC | |
| Default output voltage | –53.5V DC | |
| Maximum output power | 50A | |
| Peak-to-peak murmur voltage | ≤200mV(0~20MHz) | |
| -24VDC output | Voltage regulation accuracy | –26.4V DC | 
| Output voltage range | –22V DC~–31V DC | |
| Maximum output power | 6A | |
| AC input protection | AC input overvoltage protection point | Protection action occurs when the input single-phase voltage is greater than the AC overvoltage protection point (300V AC by default). | 
| AC input undervoltage protection point | Protection action occurs when the input single-phase voltage is less than the AC undervoltage protection point (85V AC by default). | |
| 48DC input protection | DC input overvoltage protection point | When the input voltage is greater than the overvoltage protection point (59V by default), a protective action will occur. | 
| DC input undervoltage protection point | When the input voltage is less than the undervoltage protection point (default 40V), the protection action will occur. | |
| -48DC output protection | DC output overvoltage protection point | The overvoltage protection range is: –58V DC~–60V DC | 
| -24DC output protection | DC output overvoltage protection point | The overvoltage protection range is: –30V DC~–32V DC | 
| Reliability | Mean Time Between Failures (MTBF) | 100,000 hours(25℃) | 
| Structure | Protection class | IP20 | 
| Installation mode | The ear-hook supports 19-inch and ETSI cabinet mounting | |
| Wiring Method | come late and leave late | |
| RS485 | 1 | |
| DI/DO | DI*12/DO*4 |