Views: 0 Author: Site Editor Publish Time: 2025-02-28 Origin: Site
The 24VDC rectifier module comes with the latest technology PFC and soft-switching which provides high efficiency up to 96%. Module communicated via RS485 to the master controoler.Wide input AC votlage range and software adjustable output provides safe operation condition. The output and alarm of the rectifier system can be configured by software configuration via push-botton panel.
Switched mode rectifiers are used in modular technology to convert the three-phase/ single-phase 400/230V AC voltage into the required DC voltage. The used rectifier modules can be added or replaced at any time during operation of the system (hot-plug technology).
1. Input Feature
Input | Single input |
Input Voltage Range | 90Vac to 290Vac |
Rate input Voltage | 110Vac / 220Vac |
Normal Input | 100Vac to 240Vac |
Frequency Range | 45Hz-65Hz |
Max Input Current | 10.2A±10%@176Vac/1800W |
Surge Current | Compliant Standard:ETSI300132-3 |
Efficiency | ≥90%@220Vac@ 220Vac 100% load |
PF | ≥0.99@220Vac/60A |
Leakage Current | <3.5mA@264Vac |
Input Fuse | L Wire ,Fuse 25A |
Max input Voltage | 310Vac |
2.Output Feature
Output Voltage | +24Vdc |
Output Voltage Regulation | +24±0.1Vdc |
Output Range adjustable Range | +21Vdc~+29Vdc |
Load sharing(50%~100% Loading) | ≤±5% |
Line regulation | ±0.1% |
Load regulation | ±0.5% |
Voltage precision | ±0.6% |
Min-current | 0A |
Rate current | 70A |
Peaking current | 70A |
Tempe. coefficient(1/℃) | ≤±0.02% |
Rate Capacity | 2000W(150Vac~290Vac) 1000W(90Vac~150Vac) |