To recharge any types of rechargeable batteries, for instance vented or sealed,lead-acid,Ni-Cd, the three-phase rectifiers, empoly a 6-pulse thyristor bridge, fully controlled by PCB board.
| Limit the output by dropping Diodes | |||
| Isolation transformer and Harmonic filters | |||
| Applicable international standard:IEC 60950-1 | |||
| Panel IP and panel thickness:IP20 Indoor,2mm | |||
| Rectifier efficiency:≥90% | |||
| AC&DC short circuit current:TBD based on design and below specs. | |||
| Mode of controlling output voltage current specify it should be manual /automatic:Both(Manual & Automatic,but the output voltage should be regulated. | |||
| Rectifier transformer overload capacity:The Max.rectifier capacity | |||
| Type of metering indicators:Both (Analog &Digital) | |||
| Installation type:Indoor | |||
| Type of Earthing:Solidly | |||
| Input:- | |||
| 3 phase AC Supply 400VAC±20% | |||
| 50Hz±6% | |||
| Power Factor Approx(0.7-1) | |||
| Isolation transformer | |||
| Output:- | |||
| 110VDC Regulated with ± 5% (Adjustable) | |||
| 0-100A | |||
| DC Filter | |||
| Output Ripple voltage Max 5%rms nominal DC voltage | |||
| Charging Mode Selector Switch: | |||
| The charging mode should be Automatic and Manual with independently adjustable of charging via selector switch as: | |||
| Float (Trickle) Charge | |||
| Hi-Rate (Boost) Charge | |||
| Current Limit Setting | |||
| Float and boost Charge Rating capacity:Adjustable for the batteries with capacity of (100AH-600AH) | |||
| Slow-Start: | |||
| The Slow Start function is used to prevent high current surge during powering up of the rectifier and the Circuit only operate during the start-up of the rectifier. | |||
| Typically,the design is chosen to give the slow-start ramp of I0seconds from start up. | |||
| Operation Environment | |||
| Audible Noise 55 dBA@1.5m±10% | |||
| Temperature Range -25°C to+55°C continuous | |||
| Humidity 0 to 95% @ 25°C | |||
| Altitude≥2000m above sea level. | |||
| Cooling System | |||
| Low noise Fan with Air Filter | |||
| Protection: | |||
| AC DC Surge | |||
| AC Input Over and Under Voltage Protection | |||
| AC DC Surge Suppressers | |||
| AC Input Over and Under Voltage Protection | |||
| DC output Over Voltage Protection | |||
| DC output over Current Protection | |||
| DC Output Earth Fault Protection | |||
| Metering: | |||
| AC Input Voltage Indicator | |||
| AC Input Current Indicator | |||
| DC Output Voltage Indicator(Load) | |||
| DC Output Current Indicator (Load) | |||
| DC Output Voltage Indicator(Batteries) | |||
| DC Output Current Indicator (Batteries) | |||
| Battery Status LED (Rate of Charge) | |||
| Multi Alarm system and LED Indications | |||
| Rectifier Normal Operation | |||
| Alarm sounder and Silence button | |||
| AC Input Reverse Phase Sequence LED | |||
| AC Input phase failure and Low Voltage Alarm and LED | |||
| Low Voltage Output Alarm and LED(Adjustable) | |||
| Input and Output MCB or Fuses trip Alarm | |||
| High Temp.Inside the Charger or semiconductor | |||
| Colling Fan has Failed | |||
| Ground Fault"-VE" | |||
| Ground Fault"+VE" | |||
| Charger Fail | |||
| Terminal and cabling connections | |||
| Bottom connected | |||
| Separate Terminal Block for the Input,Load and Batteries | |||
| Applications | |||
| DABS Substations. | |||
| DABS Junction Stations. |