In conventional low-voltage distribution, the utility supply sits on top and the load below, so panels normally use "top-in, bottom-out" wiring. In a PV grid-tie cabinet, however, the inverter is the power source. A common inverted layout places the inverter AC output cable into the cabinet from the top, while the grid connection cable leaves from the bottom. Visually it still looks "top-in, bottom-out," but the current direction is reversed compared with a utility-fed panel.
This inverted approach is not random rewiring; it is driven by site constraints. Inverters are often wall-mounted above or beside the cabinet, with output terminals facing upward or sideways, so a top entry keeps the run short and avoids unnecessary bends. The grid point usually ties to an underground conduit or cable trench below the cabinet, making bottom exit natural for thick, stiff cables and reducing large-radius bends inside the enclosure. When several inverters combine, top-in and bottom-out also gives a cleaner busbar path and tidier field wiring.
The trade-off is real. If a breaker is wired "bottom-in, top-out" (reverse feed), standard miniature or many molded-case breakers struggle to extinguish the arc and may cause flashover. The fix is to specify PV-rated breakers explicitly certified for reverse feed.
In short, inverted mounting is an engineering compromise that adapts to inverter position and grid exit path. It does not discard the top-in bottom-out convention; it redefines which side is source and which side is grid.