NASN 48VDC to 110VAC pure sine wave inverter, designed for railway signaling and telecommunications, converts 40-60VDC telecom battery power into stable 110VAC/60Hz. The pure sine wave inverter feature rack-mountable designs, high efficiency (≥85%), and robust protection (overload, short circuit), including automatic AC bypass for high reliability.
Voltage Range: Designed for 48VDC nominal inputs, with operating ranges generally spanning 40VDC to 60VDC, suitable for battery-backed systems.
Output Stability: Pure Sine Wave (PSW) output ensures compatibility with sensitive electronic equipment, signaling systems, and data equipment.
Reliability: Built in automatic transfer switches (ATS) from inverter to grid/generator power, critical for unattended sites.
Design & Standards: Rack-mount configurations (1U, 2U, or 4U) with built-in LCD monitoring for real-time voltage, current, and status display.
Remote Power Management optional via RS-232 port,SNMP optional.

| MODEL | T48/110-XKS | |||||||||
| Technical Index(VA) | 0.5K | 1K | 2K | 3K | 4K | 5K | 6K | 8K | 10K | |
| DC input | Rated input voltage (Vdc) | 48Vdc | ||||||||
| Rated input current (A) | 11 | 21 | 42 | 63 | 83 | 104 | 125 | N/A | N/A | |
| Allowable range of input DC voltage (Vdc) | Cutoff voltage 40V--60V Startup voltage 45.5V—57V | |||||||||
| Backward noise current | ≤10% | |||||||||
| AC by-pass input | Allowable by-pass voltage (Vac) | 132V-90V(±10V) | ||||||||
| Rated input current (A) | 4.2 | 8.3 | 16.7 | 13.6 | 26 | 41.6 | 50 | N/A | N/A | |
| By-pass conversion time (ms) | ≤5ms | |||||||||
| AC output | Rated capacity (VA) | 500 | 1K | 2K | 3K | 4K | 5K | 6K | N/A | N/A |
| Rated output power (W) | 400 | 800 | 1600 | 2400 | 3200 | 4000 | 4800 | N/A | N/A | |
| Inverter output voltage and frequency | 110Vac,50HZ/60HZ | |||||||||
| Inverter output current (A) | 3.3 | 6.7 | 13.3 | 20 | 27 | 33.3 | 40 | N/A | N/A | |
| Output voltage precision (V) | 110±1.5% | |||||||||
| Output frequency precision (Hz) | 50±0.1% Or 60±0.1% | |||||||||
| Waveform | Pure sine wave | |||||||||
| Total harmonic distortion (THD) | ≤3% (linear load) | |||||||||
| Dynamic response time | 5% (load 0←→100%) | |||||||||
| Power factor (PF) | 0.8 | |||||||||
| Overload capacity | 100%-120% 60s ; 121%-150% 10s | |||||||||
| Inversion efficiency (80% resistive load) | ≥85% | |||||||||
| By-pass conversion time (ms) | ≤5ms | |||||||||
| Working Environment | Dielectric strength (input and output) | 1500Vac, 1 minute | ||||||||
| Noise (1m) | ≤40dB | |||||||||
| Operating environment temperature | -20℃~+50℃ | |||||||||
| Humidity | 0~90%, no moisture condensation | |||||||||
| Operating altitude (m) | ≤2000 | |||||||||
| Communication | RS232 and RS485, SNMP optional | |||||||||
| Indication | LCD display | Input and output voltage, frequency, output current, temperature, percentage, etc. | ||||||||
| inverter status | Normal mains, normal inversion, battery under-voltage and output overload | |||||||||
| Mechanical size | Standard rack | 347*482*88 | 430*482*88 | N/A | ||||||
| (Depth × Width × Height) (mm) | ||||||||||
| Protection function | DC input reverse polarity protection | Available | N/A | |||||||
| Normal protections | Input under-voltage and overvoltage, output overload and short circuit protections, etc. | |||||||||