NASN TL series inverters is a dual conversion online, single-phase input, single-phase output uninterruptible power supply device. The product has high efficiency and reliability, providing reliable and high-quality AC power for your equipment. This series of 2-3KVA online inverter power supplies is compact in size, convenient for customers to use, and particularly suitable for basic equipment of users such as power, telecommunications, mobile, Unicom, and railways.

| MODEL | TL48/220-2KL | TL48/220-3KL | ||||
| Rated Capacity | 2KVA/1600W | 3KVA/2400W | ||||
| AC Input | Input Method | L+N+PE | ||||
| Input Voltage Range | (110±5to296±5)Vac | |||||
| Input Frequency Range | (45±0.5to55±0.5)Hz/(55±0.5to65±0.5)Hz Adaptive | |||||
| Input Power Factor | >0.98 | |||||
| Bypass Voltage Range | (80±5 to 262±5)Vac | |||||
| AC Output | Rated Output Voltage | 220Vac(±1.5%) | ||||
| Output Power Factor | 0.8 | |||||
| Output Frequency | AC Mode: Synchronized with the grid;Battery Mode: 50/60Hz | |||||
| Waveform Distortion | THD<3%(Linear Load);THD<5%(Non-linear Load) | |||||
| Transfer Time |  AC to Inverter Mode   ←→    Battery Inverter Mode:0ms | |||||
|  Bypass Mode   ←→     AC to Inverter Mode:≤4ms | ||||||
| Overload Capacity | 105±5%≤Load≤150±5%:30s to bypass; | |||||
| >150±5%:300ms to bypass | ||||||
| Inverter Efficiency | AC Operation≥92%,DC Operation≥85% | |||||
| DC Input | Rated Input Voltage | 48Vdc | ||||
| Upper Voltage Limit | Shutdown Voltage 60V+1V | |||||
| Recovery Voltage 58V+1V | ||||||
| Lower Voltage Limit | Shutdown Voltage 40.0V+1V | |||||
| Recovery Voltage 42.0V+1V | ||||||
| Interface | HMI | LED+LCD | ||||
| Communication | Communication Interface | Standard Smart RS232/RS485 Communication Interface | ||||
| Dry Contact Output | 4 Passive Dry Contact Outputs | |||||
| Environment | Noise (1m) | ≤45dB | ||||
| Operating Temperature | 0℃~40℃ | |||||
| Operating Humidity | 0~95% No Condensation | |||||
| Storage Temperature | -40℃~50℃ | |||||
| Altitude | No derating below 1000m. Above 1000m, derate by 1% for every 100m increase in altitude | |||||
| Dimensions | Width*Depth*Height (mm) | 482*392.5*88 | ||||
| Weight | KG | 10.5 | 11 | |||