Views: 0 Author: Site Editor Publish Time: 2024-05-30 Origin: Site
Utility Battery Chargers 125VDC is Industrial Dc Power solutions for the Utility lndustry, Oil &Gas Industrial and Electrical applications.
Stationary battery chargers with input voltages of 400VAC±10%. Single Phase or Three Phase. Output Power of 125VDC,20, 40, 60, 80 or 100 Amps.
It's switch-mode modular power supply in a compact rack-mounted size.
| MODEL | A220/125-20M1 | A220/125-40M2 | A380/125-60M3 | A380/125-100M5 | A380/125-140M7 | |
| Configuration | 1pcs 125V/20A module +1pcs monitor | 2pcs 125V/20A module +1pcs monitor | 3pcs 125V/20A module +1pcs monitor | 5pcs 125V/20A module +1pcs monitor | 7pcs 125V/20A module +1pcs monitor | |
| Environmental | Operating temperature | -40°C ~ 55°C | ||||
| Storage temperature | -40°C ~ 70°C | |||||
| Relative humidity | ≤ 90%RH (30°C) | |||||
| Communication | RS485 or SNMP | |||||
| Altitude | ≤ 2000m (derating is necessary above 2,000m) | |||||
| AC Input | AC input system | L+N+PE/220Vac | L1+L2+L3+N/380Vac | |||
| Input voltage range | 90VAC ~ 280VAC | 323-437VAC | ||||
| Input AC voltage frequency | 45Hz ~ 65Hz | |||||
| Max input current | ≤28.4A | |||||
| Power factor | ≥ 0.99 | |||||
| DC Output | Nominal output voltage | 110VDC | ||||
| Rated output voltage | 125VDC | |||||
| Rated Output Capacity | 2.5kW | 5kW | 7.5kW | 12.5kW | 17.5kW | |
| Output DC voltage | 90VDC ~ -150VDC | |||||
| Output DC current | 20A | 40A | 60A | 100A | 140A | |
| Voltage set-point accuracy | ≤ 1% | |||||
| Efficiency | ≥ 93.2% | |||||
| Noise (peak-peak) | ≤ 200mV (0 ~ 20MHz) | |||||
| Weighted noise | ≤ 2mV (300Hz ~ 3400Hz) | |||||
| AC Input Alarm and Protection | AC input over-voltage alarm point | Default: 280VAC ± 5VAC* | ||||
| AC input under-voltage alarm point | Default: 176VAC ± 5VAC | |||||
| AC input over-voltage protection recovery difference | Default: 295VAC ± 5VAC, 10VAC lower than the AC input over-voltage protection point | |||||
| AC input under-voltage protection point | Default: 180VAC ± 5VAC* | |||||
| DC Output Alarm And Protection | DC output over-voltage alarm point | Default:149VDC ± 0.5VDC* | ||||
| DC output under-voltage alarm point | Default:90VDC ± 0.5VDC* | |||||
| DC output over-voltage protection point | Default: 97.2VDC ± 0.5VDC* | |||||
| LLVD | Default: 99VDC ± 0.5VDC* | |||||
| BLVD | Default: 97.2VDC ± 0.5VDC* | |||||
| Rectifier | Load sharing | The rectifiers can work in parallel and share the current. The unbalance is better than ± 5% rated output current. | ||||
| Derated by input (at 45°C) | The rectifier can output power of 100% with input voltage of ≥154VAC; The rectifier can output power capacity 1200W with input voltage <154VAC; Rectifiers under-voltage stop with input voltage of 85VAC | |||||